[Date Prev][Date Next][Thread Prev][Thread Next][Date Index][Thread Index]
DoS vulnerability in Siemens S7-1200 PLCs
- To: "bugtraq@xxxxxxxxxxxxxxxxx" <bugtraq@xxxxxxxxxxxxxxxxx>
- Subject: DoS vulnerability in Siemens S7-1200 PLCs
- From: Arne Vidström <arne.vidstrom@xxxxxx>
- Date: Thu, 20 Dec 2012 17:07:13 +0100
Hi all,
I have found a DoS vulnerability in the Siemens S7-1200 PLCs. It is present in
firmware versions 2 and 3. After an exchange of specially crafted packets to
TCP port 102 the PLC shuts down. The red, green and yellow status LEDs start
flashing. All outputs are shut off. The device stops listening at port 102 and
becomes completely non-responsive. Sometimes a few status messages are sent
before it shuts down. They state that a serious firmware error has occurred and
that the PLC is defective. Power cycling the PLC restores operation though.
More information can be found in the Siemens advisory:
http://www.siemens.com/corporate-technology/pool/de/forschungsfelder/siemens_security_advisory_ssa-724606.pdf
Best regards /Arne
-
Arne Vidström
Swedish Defence Research Agency (FOI)
http://www.foi.se/en/Our-Knowledge/Information-Security-and-Communication/Information-Security